Motor Protection Circuit Breaker
3RV

3RV

3rv1011-motor-protection-circuit-breaker3RV1011
3rv1012-motor-protection-circuit-breaker3RV1012

Application:

  • DZS8(3RV) Series Motor Protection Circuit Breaker are mainly used for the overload, short-circuit and phase-failure protection for motors in the circuit of AC50/60Hz, Rated operating voltage up to 660V, Rated operating current from 0.11A to 25A. They can be also used for circuit protection in the circuit of 0.11 ~ 25A.

The Model No. and Meaning
2007320155340909

Technical Data

Rated Current (A) Applicable 3-phase AC electro motor 1)pn (KW) Setting current scope of the overload releaser (A) Momentar excess current releaser (A) Short-circuit and breaking capacity under the AC400V (KA) Circuit breaker Order NO.
0.16 0.04 0.11-0.16 2.1 100 3RV1011-0AA10
0.2 0.06 0.14-0.2 2.6 100 3RV1011-0BA10
0.25 0.06 0.18-0.25 3.3 100 3RV1011-0CA10
0.32 0.09 0.22-0.32 4.2 100 3RV1011-0DA10
0.4 0.09 0.28-0.4 5.2 100 3RV1011-0EA10
0.5 0.12 0.35-0.5 6.5 100 3RV1011-0FA10
0.63 0.18 0.45-0.63 8.2 100 3RV1011-0GA10
0.8 0.18 0.55-0.8 10 100 3RV1011-0HA10
1 0.25 0.7-1 13 100 3RV1011-0JA10
1.25 0.37 0.9-1.25 16 100 3RV1011-0KA10
1.6 0.55 1.1-1.6 21 100 3RV1011-0AA10
2 0.75 1.4-2 26 100 3RV1011-0BA10
2.5 0.75 1.8-2.5 33 100 3RV1011-0CA10
3.2 1.1 2.2-3.2 42 100 3RV1011-0DA10
4 1.5 2.8-4 52 100 3RV1011-0EA10
5 1.5 3.5-5 65 100 3RV1011-0FA10
6.3 2.2 4.5-6.3 82 100 3RV1011-0GA10
8 3 5.5-8 104 50 3RV1011-0HA10
10 4 7-10 130 50 3RV1011-0JA10
12 5.5 9-12 156 50 3RV1011-0KA10
0.16 0.04 0.11-0.16 2.1 100 3RV1021-0AA10
0.2 0.06 0.14-0.2 2.6 100 3RV1021-0BA10
0.25 0.06 0.18-0.25 3.3 100 3RV1021-0CA10
0.32 0.09 0.22-0.32 4.2 100 3RV1021-0DA10
0.4 0.09 0.28-0.4 5.2 100 3RV1021-0EA10
0.5 0.12 0.35-0.5 6.5 100 3RV1021-0FA10
0.63 0.18 0.45-0.63 8.2 100 3RV1021-0GA10
0.8 0.18 0.55-0.8 10 100 3RV1021-0HA10
1 0.25 0.7-1 13 100 3RV1021-0JA10
1.25 0.37 0.9-1.25 16 100 3RV1021-0KA10
1.6 0.55 1.1-1.6 21 100 3RV1021-0AA10
2 0.75 1.4-2 26 100 3RV1021-0BA10
2.5 0.75 1.8-2.5 33 100 3RV1021-0CA10
3.2 1.1 2.2-3.2 42 100 3RV1021-0DA10
4 1.5 2.8-4 52 100 3RV1021-0EA10
5 1.5 3.5-5 65 100 3RV1021-0FA10
6.3 2.2 4.5-6.3 82 100 3RV1021-0GA10
8 3 5.5-8 104 100 3RV1021-0HA10
10 4 7-10 130 100 3RV1021-0JA10
12.5 5.5 9-12 163 100 3RV1021-0KA10
16 7.5 11-16 208 50 3RV1021-0AA10
20 7.5 14-20 260 50 3RV1021-0BA10
22 11 17-22 286 50 3RV1021-0CA10
25 11 20-25 325 50 3RV1021-0DA10

1) The recommended data for 4-phase standard electromotor under the condition of AC50Hz, 400V. What affects the products most is the factual starting data and rated sata of the protected electomotor.The protection characteristic against over-current of the breaker

The multiple of rated current Starting state Stipulated time Prospective result The temp. of ambient air
1.05 Cold state t≤2h No disjointing +20°C ±2°C
1.2 Hot state(rises up to the stipulated current after following the test of no. 1) t<2h Disjointing +20°C ±2°C
1.5 One-time commuting current starts after the thermal equilibrium t<2min Disjointing +20°C ±2°C
7.2 Cold state t<2≤10s Disjointing +20°C ±2°C

Tripping Current (Average Value)

2007320155340909
Tripping Current (Average Value)

Characteristic curves

Characteristic Curves

Dimensioned

3rv-motor-protection-circuit-breaker-dimension
Dimensioned
  • 1) 2-pole side supplementary switch;
  • 2) Signal switch or 4-pole side supplementary switch;
  • 3) Supplementary releaser;
  • 4) Transverse supplementary contact;
  • 5) Patching slice for screw installation;
  • 6) Punching template;
  • 7) 35m DIN-rail installation;
  • 8) Lock the location of breaking the diameter of the staple is 3.5mm or 4.5mm.