  • The products provide protection against earth leakage faults,overloads,short circuits and overvoltage in commercial and domestic installation.
  • The RCBO with both disconnected neutral and phase guarantees its proper actuation against earth leakage fults even when the neutral and phase are wongly connected.
  • The electronic RCBO incorporate a filtering device preventing the risks of unwanted due to transient voltages and transient currents.
  • Positive contact indication in accordance with 16th edition of the IEE wiring regulations
  • Standard: GB16917.1, IEC61008

Advantage

  • Our products have the guarantee period of 36 calendar months,that is a high quality and reliability;
  • Our products have an excellent ratio between price and quality ,you can possess them by competitive price and high quality;
  • The fast and flexible production form aim at the customer require;
  • The deliveries exactly in accordance with customer orders
  • The fast transportation.
  • Adopt electromagnetic style release , can play a leak electricity and electric shock protecting role while breaking in zero Line.

Construction Features:

  • Measuring component and buckling component of products is located between enter line end and entrance line end ;
  • Movement characteristic of products can not be changed with outside mechanical tool ;
  • The operating organization has the free function to take off and buckle;
  • Operate part can not be taken down from the shell outer of products , the shell can not influence the operating organization to work , the accessory group which replace the feelers pressure, should guarantee the feelers pressure does not change while running.

Normal operation and mounting requirement

  • Circumstance temperature -5°C ~ +40°C, average temperature within 24h not exceeding +35°C.
  • Altitude above sea level less than 2000 m.
  • Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
  • Installation class II or III.
  • Pollution class 2.
  • Installation method DIN Rail mounting type.
  • The external magnetism shall not be more than 5 times of terrestrial one.
  • Product shall be installed at the place where there shall be no severe impact and vibration.
  • Product shall be vertically mounted onto standard Din rail 35mm.

Technical Data

Type VL6-32
Number of poles 1P+N
Rated Current(In) 6, 10, 16, 20, 25, 32, 40A
Rated operating current( I△n) 30, 100, 300mA
Rated Voltage(Un) 230(240)VAC
Residual operating current scope 0.5I△n~I△n
Residual current off-time ≤0.3s
Type A, AC
Ultimate short-circuit breaking capacity (Inc) 3000A
Endurance ≥4000
Terminal protection IP20